Warning: file_get_contents(http://www.geoplugin.net/json.gp?ip=13.58.190.176): failed to open stream: HTTP request failed! HTTP/1.1 429 Too Many Requests in /www/wwwroot/captainmro/website/vqmod/vqcache/vq2-storage_modification_catalog_controller_startup_startup.php on line 192 Rosemount 8732E Field Mount Magnetic Flow Meter Transmitter
Menu
Your Cart

Rosemount 8732E Field Mount Magnetic Flow Meter Transmitter

 Rosemount 8732E Field Mount Magnetic Flow Meter Transmitter
Rosemount 8732E Field Mount Magnetic Flow Meter Transmitter
$0.00
Ex Tax: $0.00
  • Stock: In Stock
  • Model: 8732ESR1F1N0M5

SKU: 8732ESR1F1N0M5

Rosemount 8732E Field Mount Magnetic Flow Meter Transmitter

Rosemount No. 8732ESR1F1N0M5

A dual-compartment transmitter housing provides isolation from the external environment. Advanced diagnostics and through-the-glass Local Operator Interface offer unparalleled process insight.

Specifications

Sensor compatibility: Compatible with Rosemount 8705, 8711, and 8721sensors. Compatible with AC and DC powered sensors ofother manufacturers.
Transmitter coil drive current: 500mA
Flow rate range : Capable of processing signals from fluids that are travelingbetween 0.04 and 39 ft/s (0.01 to 12 m/s) for both forwardand reverse flow in all sensor sizes. Full scale continuouslyadjustable between –39 and 39 ft/s (–12 to 12 m/s).
Conductivity limits: Process liquid must have a conductivity of5 microSiemens/cm (5 micromhos/cm) or greater.
Power supply: 90 – 250VAC, 50/60Hz or 12 – 42VDC
Line power fuses
90-250VAC systems
1A, 250V, I2t, 1.5 A2s Rating, Fast ActingBussman AGC-1, Littlefuse 31201.5HXP
12-42VDC systems
3 Amp, 250V, I2t, 14 A2s Rating, Fast ActingBel Fuse 3AG 3-R, Littelfuse 312003P, Schurter 0034.5135
Line power fuses
15W maximum – DC
40VA maximum – AC
Switch-on current
AC: Maximum 35.7A (< 5ms) at 250VAC
DC: Maximum 42A (< 5ms) at 42VDC